| Sign In | Join Free | My components-electronic.com |
|
Rated Voltage : 24kV
Breaking Times of LBS with Full Capacity : 100Times
Mechanical Endurance : 10000Times
Rated Short-circuit Making Current of Main Circuit and Earthing Circuit : 63kA
Brand Name : ChangYun
Model Number : FLRN36-1224
Rated SF₆ Gas Pressure (Ambient Temp. 20℃) : 0.045MPa
1 min Power Frequency Withstand Voltage : 65/79kV
Main Circuit : ≤75μΩ
Rated Frequency : 50HZ
Breaking Current of Capacitor Bank : 630A
Rated Current : 630A
Rated Peak Withstand Current of Main Circuit and Earthing Circuit : 63kA
Rated Transfer Current : 1500A
Place of Origin : China
Lightning Impulse Withstand Voltage : 125/145kV
Rated Short-time Withstand Current of Main Circuit and Earthing Circuit : 50/2kA/s
The FLN36-24D/T630-20-230 SF₆ load-break switch is a compact, gas-insulated switching device designed for 12kV/50Hz three-phase power systems. Widely used in ring main units (RMUs), compact substations, and distribution networks, it performs core functions of load current switching, circuit isolation, and earthing, serving as a key component for power distribution control and protection.
Use conditions
Ambient air temperature: -35℃~+40℃
Altitude: ≤1000m
Relative humidity: daily average of not more than 95%; the monthly average of not more than 90%
The ambient air does not contain corrosive gases, combustible gases or vapors.
There is no frequent vibration.
Ideal for use in:
|
|
FLN36-24D/T630-20-230 SF₆ load-break switch Images |